Heat Shrink Technology

Home / Heat Shrink Technology

Damaged Cable Repair Kit

Screen Layer Damage (for STA Cable) (ADCRK-3)

Kit Contents:

  • Abrasive Paper/Aloxite Emery Tape
  • Constant Force Spring Roll/ Jublee Clamp
  • H₂O Proofing Insulating Tape
  • Metal Sheilding Mesh/ GI Mesh
  • Armor Tape
  • EPR High Voltage Insulating Tape

  • Function Repair:

  • Mechanical Protection
  • H₂O proofing & Corrosion Protection
  • Screen Recovery

  • Procedure:

  • Cut off the Screen & armor layer from the damaged cable.
  • Tighten it up with spring rolls.
  • Abrase the cable jacket.
  • Wrap shielding mesh around the cable for 2 layer.
  • Tighten it up with spring rolls.
  • Wrap around the cable & EPR high voltage insulating tape for 2 layer.
  • Wrap H₂O proofing insulating tape for 3 layer.
  • Warp armor tape around the cable.
  • Repairing completed.

  • Screen Layer Damage (UA) (ADCRK-4)

    Kit Contents:

  • Abrasive Paper /Aloxite Emery Tape
  • Abrasion Resistant PVC Tape
  • Constant Force Spring Roll/ Jublee Clamp
  • Metal Sheilding Mesh/ GI Mesh
  • Cable Jacket Repair Tape

  • Function Repair:

  • Mechanical Protection
  • H₂O proofing & Corrosion Protection
  • Screen Recovery

  • Procedure:

  • Cut off the Screen & armor layer from the damaged cable.
  • Cut off the copper screen layer.
  • Tighten it up with spring rolls.
  • Abrase the cable jacket.
  • Wrap shielding mesh around the cable for 2 layer.
  • Tighten it up with spring rolls.
  • Abrase cable jacket repair tape for 3 layer.
  • Wrap abrasive resistant PVC tape on both ends.
  • Repairing completed.

  • * We reserve the right to make any technical changes or modify in content.